Optional LCD Display
D0-06LCD [$73]
The DL06 offers the D0-06LCD optional snap-in LCD display with the following features:
- Two-line x 16-character display simply snaps into the face of the DL06. No cable or special mounting required!
- ESC, MENU and ENT keys, along with four arrow keys allow for easy and intuitive navigation
- Password protection capabilities available for system parameters like date and time
- Backlight can be turned off for bright locations

|
|
The DL06 is our first micro PLC to combine its fixed I/O of 20 inputs and 16 outputs with four option card slots for expansion (discrete, analog, communication modules), all in the same package. With the DL06, you can use the same PLC panel layout for all applications from 36 to 100 I/O. Check out some of the other practical features the DL06 has to offer:
- 14.8 K of total memory
- 229 instructions, including 8 PID loops
- Two communication ports, including RS232/422/485 capability
- Supports networking for MODBUS RTU master/slave, ASCII in/out, and a DeviceNET slave option card
- Integrated high-speed inputs and pulse output
- Built-in real-time clock/calendar
- Optional LCD display for operator interface or maintenance troubleshooting
NOTE: PID (Proportional, integral, derivative) control: Control algorithm that is used to closely control processes such as temperature, mixture, position, and velocity. The proportional portion takes care of the magnitude of the error. The derivative compensates for the rate of error change. The integral takes care of small errors over time.
AC-powered PLC units
- D0-06DD1 (with sinking outputs) [$199]- 20 DC in / 16 DC out, 110/220 VAC power supply, with 0.3 A 24 VDC auxiliary device power supply. 14.8 K words total (7679 words ladder - flash, 7488 words V-memory), RLL/RLLPLUS programming (DirectSOFT5 Version 4.0 or higher), two built-in RS232C communication ports. Secondary communications port supports RS232C/ RS422/ RS485, DirectNET Master/Slave, MODBUS RTU, Master/Slave, and ASCII In/Out.
Inputs: 20 DC inputs, 12-24 VDC current sinking/sourcing, 5 isolated commons (4 inputs per common).
First 3 inputs are configurable in one of several high-speed I/O features such as 7 KHz counter input, pulse catch input, or interrupt input (not available when using pulse output).
Outputs: 16 DC outputs, 12-24 VDC current sinking, 1.0 A/point maximum, 4 commons nonisolated (4 points per common).
2 outputs are configurable for independent CW/CCW pulse train output or step and direction pulse output up to 10 KHz (0.5 A/point) (Not available when using high-speed inputs).
- D0-06DD2 (with sourcing outputs) [$199]- 20 DC in / 16 DC out, 110/220 VAC power supply, with 0.3 A 24 VDC auxiliary device power supply. 14.8 K words total (7679 words ladder - flash, 7488 words V-memory), RLL/RLLPLUS programming (DirectSOFT5 Version 4.0 or higher), two built-in RS232C communication ports. Secondary communications port supports RS232C/ RS422/ RS485, DirectNET Master/Slave, MODBUS RTU, Master/Slave, and ASCII In/Out.
Inputs: 20 DC inputs, 12-24 VDC current sinking/sourcing, 5 isolated commons (4 inputs per common).
First 3 inputs are configurable in one of several high-speed I/O features such as 7 KHz counter input, pulse catch input, or interrupt input (not available when using pulse output).
Outputs: 16 DC outputs, 12-24 VDC current sourcing 1.0 A/point maximum, 4 commons nonisolated (4 points per common).
2 outputs are configurable for independent CW/CCW pulse train output or step and direction pulse output up to 10 KHz (0.5 A/point) (Not available when using high-speed inputs).
- D0-06DR [$229] - 20 DC in / 16 Relay out, 110/220 VAC power supply, with 0.3 A 24 VDC auxiliary device power supply. 14.8 K words total (7679 words ladder - flash, 7488 words V-memory), RLL/RLLPLUS programming (DirectSOFT5 Version 4.0 or higher), two built-in RS232C communication ports. Secondary communications port supports RS232C/ RS422/ RS485, DirectNET Master/Slave, MODBUS RTU, Master/Slave, and ASCII In/Out.
Inputs: 20 DC inputs, 12-24 VDC current sinking/sourcing, 5 isolated commons (4 inputs per common).
First 3 inputs are configurable in one of several high-speed I/O features such as 7 KHz counter input, pulse catch input, or interrupt input.
Outputs: 16 Relay outputs, 6-27 VDC, 6-240 VAC, 2 A/point maximum, 4 isolated commons (4 points per common).
- D0-06DA [$259] - 20 DC in / 16 AC out, 110/220 VAC power supply, with 0.3 A 24 VDC auxiliary device power supply. 14.8 K words total (7679 words ladder - flash, 7488 words V-memory), RLL/RLLPLUS programming (DirectSOFT5 Version 4.0 or higher), two built-in RS232C communication ports. Secondary communications port supports RS232C/ RS422/ RS485, DirectNET Master/Slave, MODBUS RTU, Master/Slave, and ASCII In/Out.
Inputs: 20 DC inputs, 12-24 VDC current sinking/sourcing, 5 isolated commons (4 inputs per common).
First 3 inputs are configurable in one of several high-speed I/O features such as 7 KHz counter input, pulse catch input, or interrupt input.
Outputs: 16 AC outputs, 17-240 VAC, 0.5 A/point maximum, 2 isolated commons (8 points per common).
- D0-06AR [$259]- 20 AC in / 16 Relay out, 110/220 VAC power supply, with 0.3 A 24 VDC auxiliary device power supply. 14.8 K words total (7679 words ladder - flash, 7488 words V-memory), RLL/RLLPLUS programming (DirectSOFT5 Version 4.0 or higher), two built-in RS232C communication ports. Secondary communications port supports RS232C/ RS422/ RS485, DirectNET Master/Slave, MODBUS RTU, Master/Slave, and ASCII In/Out.
Inputs: 20 AC inputs, 90-120 VAC, 5 isolated commons (4 inputs per common).
Outputs: 16 Relay outputs, 6-27 VDC, 6-240 VAC, 2 A/point maximum, 4 isolated commons (4 points per common).
- D0-06AA [$275] - 20 AC in / 16 AC out, 110/220 VAC power supply. 14.8 K words total (7679 words ladder - flash, 7488 words V-memory), RLL/RLLPLUS programming (DirectSOFT5 Version 4.0 or higher), two built-in RS232C communication ports. Secondary communications port supports RS232C/ RS422/ RS485, DirectNET Master/Slave, MODBUS RTU, Master/Slave, and ASCII In/Out.
Inputs: 20 AC inputs, 90-120 VAC, 5 isolated commons (4 inputs per common).
Outputs: 16 AC outputs, 17-240 VAC, 0.5 A/point maximum, 2 isolated commons (8 points per common).
Back to top
DC-powered PLC units
- D0-06DD1-D (with sinking outputs) [$199]- 20 DC in / 16 DC out, 12/24 VDC power supply (requires 12-24 VDC power). 14.8 K words total (7679 words ladder - flash, 7488 words V-memory), RLL/RLLPLUS programming (DirectSOFT5 Version 4.0 or higher), two built-in RS232C communication ports. Secondary communications port supports RS232C/ RS422/ RS485, DirectNET Master/Slave, MODBUS RTU, Master/Slave, and ASCII In/Out.
Inputs: 20 DC inputs, 12-24 VDC current sinking/sourcing, 5 isolated commons (4 inputs per common).
First 3 inputs are configurable in one of several high-speed I/O features such as 7 KHz counter input, pulse catch input, or interrupt input (not available when using pulse output).
Outputs: 16 DC outputs, 12-24 VDC current sinking, 1.0 A/point maximum, 4 commons non-isolated (4 points per common).
2 outputs are configurable for independent CW/CCW pulse train output or step and direction pulse output up to 10 KHz (0.5 A/point) (Not available when using high-speed inputs).
- D0-06DD2-D (with sourcing outputs) [$199]- 20 DC in / 16 DC out, 12/24 VDC power supply (requires 12-24 VDC power). 14.8 K words total (7679 words ladder - flash, 7488 words V-memory), RLL/RLLPLUS programming (DirectSOFT5 Version 4.0 or higher), two built-in RS232C communication ports. Secondary communications port supports RS232C/ RS422/ RS485, DirectNET Master/Slave, MODBUS RTU, Master/Slave, and ASCII In/Out.
Inputs: 20 DC inputs, 12-24 VDC current sinking/sourcing, 5 isolated commons (4 inputs per common).
First 4 inputs are configurable in one of several high-speed I/O features such as 7 KHz counter input, pulse catch input, or interrupt input (Not available when using pulse output).
Outputs: 16 DC outputs, 12-24 VDC current sourcing, 1.0 A/point maximum, 4 commons non-isolated (4 points per common). 2 outputs are configurable for independent CW/CCW pulse train output or step and direction pulse output up to 10 KHz (0.5 A/point) (Not available when using high-speed inputs).
- D0-06DR-D [$239]- 20 DC in / 16 Relay out, 12/24 VDC power supply (requires 12-24 VDC power). 14.8 K words total (7679 words ladder - flash, 7488 words V-memory), RLL/RLLPLUS programming (DirectSOFT5 Version 4.0 or higher), two built-in RS232C communication ports. Secondary communications port supports RS232C/ RS422/ RS485, DirectNET Master/Slave, MODBUS RTU, Master/Slave, and ASCII In/Out.
Inputs: 20 DC inputs, 12-24 VDC current sinking/sourcing, 5 isolated commons (4 inputs per common).
First 3 inputs are configurable in one of several high-speed I/O features such as 7 KHz counter input, pulse catch input, or interrupt input.
Outputs: 16 Relay outputs, 6-27 VDC, 6-240 VAC, 2 A/point maximum, 4 isolated commons (4 points per common).
Back to top
LCD Display
D0-06LCD [$73]
The DL06 offers the D0-06LCD optional snap-in LCD display with the following features:
Two-line x 16-character display simply snaps into the face of the DL06. No cable or special mounting required!
ESC, MENU and ENT keys, along with four arrow keys allow for easy and intuitive navigation
Password protection capabilities available for system parameters like date and time
Backlight can be turned off for bright locations |