DirectLOGIC PLCs - the most practical PLCs in the industry......from AutomationDirect go back to DirectLOGIC home AutomationDirect online store

DirectLOGIC 06 & DL05

Analog Input/OutputDL05/06 PLC Discrete Modules DL05/06 PLC Discrete Modules

Several bases & modules are available for the DL06 | Download DL05 & 06 unit Specs (PDF)

Discrete IO Option Modules

purchase PLCs
New Drag n' Drop PLC builder: DL06 PLC [check it out]
Go to our online store
Shop for PLCs now
Save now on automation products

NOTE: New option modules may not be supported by CPUs purchased prior to the modules release.
Be sure to check for the latest firmware for your PLC. You can refer to the module specification page on our main Web site for this information, or find it in our free catalog.

Here is the direct link to the Firmware Upgrade section of our Web site where you can find the firmware revision histories, the latest files and tools required to download the firmware into your CPU.

Analog, DeviceNET, Ethernet, data communications, high-speed counting/ pulse output, thermocouple input, RTD temperature input and Profibus option modules for the DirectLOGIC 06 (DL06) programmable logic controller are also available.

The discrete I/O option cards allow the DL06 PLC to expand with the needs of your industrial process control applications for just a few dollars more. Combine our 16-point discrete output modules with ZIPLink relay modules to control high current loads, such as air solenoids or hydraulic valves.

Available discrete modules include:

DirectLOGIC discete modules
F0-08NA-1 - 8 point 110 VAC input module. [data sheet] (pdf)
1 common (2 common terminals), removable terminal block
DirectLOGIC discete modules
D0-10ND3 - 10 point 12-24 VDC current sinking/sourcing input module. [data sheet] (pdf)
2 isolated commons (5 points per common), removable terminal
DirectLOGIC discete modules
D0-10ND3F - 10-point 12-24 VDC current sinking/ sourcing, input module. [data sheet] (pdf)
Fast response, 2 isolated commons (5 points per common), removable terminal.
DirectLOGIC discete modules
D0-16ND3 - 16 point 20-28 VDC current sinking/sourcing input module. [data sheet] (pdf)
4 isolated commons(4 points per common). One pre-wired ZIPLink cable ( 0.5 meter) and terminal block connector module required for this I/O module.
DirectLOGIC discete modules
D0-10TD1 - 10 point 12-24 VDC current sinking output module. [data sheet] (pdf)
2 commons non-isolated (5 points per common), 0.3 A/point, 1.5 A/common, removable terminal, no fuse
DirectLOGIC discete modules
D0-10TD2 - 10 point 12-24 VDC current sourcing output module.[data sheet] (pdf)
2 commons non-isolated (5 points per common), 0.3 A/point, 1.5 A/common, removable terminal, no fuse
DirectLOGIC discete modules
D0-16TD1 - 16 point 12-24 VDC current sinking output module. [data sheet] (pdf)
2 commons non-isolated (5 points per common), 0.3 A/point, 1.5 A/common, removable terminal, no fuse. One pre-wired ZIPLink cable ( 0.5 meter) and terminal block connector module required for this I/O module.
DirectLOGIC discete modules
D0-16TD2 - 16 point 12-24 VDC current sourcing output module. [data sheet] (pdf)
2 commons non-isolated (8 points per common), 0.1 A/point, .8 A/common, removable terminal, no fuse. One pre-wired ZIPLink cable ( 0.5 meter) and terminal block connector module required for this I/O module. See Compatibility Matrix in the ZIPLink technical section to choose cable and connector module.
DirectLOGIC discete modules
F0-04TRS - 4 point 5-30 VDC or 5-125 VAC isolated relay output module. [data sheet] (pdf)
2 Form A (SPST) relays, 2 Form C (SPDT) relays, 4 isolated commons, 3 A/point, replaceable fuse, removable terminal block.
DirectLOGIC discete modules
D0-08TR - 8 point 6-27 VDC or 6-240 VAC relay output module. [data sheet] (pdf)
8 Form A (SPST) relays, 2 isolated commons, 1 A/point, 4 A/common, removable terminal
DirectLOGIC discete modules
D0-08CDD1 - 4 point 12-24 VDC current sinking/sourcing input. [data sheet] (pdf)
1 common, 4 point 12-24 VDC sinking output, 0.3 A/point, 1.2 A/module, removable terminal, no fuse
DirectLOGIC discete modules
D0-07CDR - 4 point 12-24 VDC current sinking/sourcing input. [data sheet] (pdf)
1 common, 3 point relay output, 3 Form A (SPST) relays 1 A/point, 3 A/module, 1 common, no fuse

DirectLOGIC discete modules
F0-08SIM - 8 point input simulator module [data sheet] (pdf)
5 VDC base power required (1 mA).

 

© 2009 AutomationDirect.com All rights reserved. All prices are U.S. list prices. AutomationDirect prices are from April 2008 Price List.

E-mail contact: Comments/Suggestions/Web site problems