Topic: CL116
|
Com Port 3 Setup Details |
|
|
|
|
|
|
Description |
The Com Port Setup Details dialog displays current settings of the selected Port. Com Port 3 is used for General Communications, acting as a Master or Slave, using Modbus (RTU) or ASCII protocol. |
|
|
|
|
|
|
|
Note: The Com Port setup is stored in the Flash EEPROM in the CLICK CPU module. This means you MUST download the user project into the CLICK PLC after you make any changes in the Com Port Setup. |
|
|
|
|
|
Setup |
1 Port: Select Port 3 from the drop down list to populate this dialog with current Port 3 setups. 2 Protocol: Port 3 supports Modbus or ASCII Protocol. Select the Protocol appropriate for your application from the drop down list. If this option is grayed out, it means one or more Receive/Send instructions are using this Com Port in the ladder program already. You can not change the protocol until you delete those instructions. 3 Basic Configuration: This field covers the Basic setup parameters that are necessary to use this Com Port. 4 Node Address (1-247) [MODBUS Only]: If you use this Com Port as MODBUS Master, please enter 1. If you use this Com Port as a MODBUS Slave, enter a MODBUS Node Address between 1 and 247. The Node Address needs to be unique in the network. 5 Baud Rate: Select a Baud Rate from the drop down list to match the Baud Rate setup of the network. 6 Parity: Select the Parity Bit setup from the Odd, Even and None to match the Parity setup of the network. 7 Stop Bit: Select the Bit Length of the Stop Bit between 1 and 2 to match the Stop Bit setup of the network. 8 Communication Data (bit) [ASCII only]: Select the Data Bit Length of the ASCII data between 7 and 8 to match the Data Bit Length setup of the external communication device. 9 Advanced Configuration: This field covers the Advanced setup parameters that are optional to use for Port 3. 10 Time-out Setting [MODBUS Only]: This parameter defines the Maximum acceptable response delay time from the MODBUS Slaves after the MODBUS Master sent a request to the Slaves. Select a Time-out Setting time between 100ms and 30sec from the drop down list. If the response delay time from a MODBUS Slave exceeds this setup, a communication error occurs and System Control Bit SC103 (Port 3 Error Flag) turns ON.
11 Character Time-out (2-1000ms) [MODBUS Only]: This parameter defines the Maximum acceptable delay time between each Character (byte data) in the response from the MODBUS Slave. Enter a Character Time-out value between 2ms and 1000ms. If the delay time between each Character exceeds this setup, a Communication Error occurs and System Control Bit SC103 (Port 3 Error Flag) turns ON.
12 Response Delay Time (0-5000ms) [MODBUS Only]: When this Port 3 is used to communicate as a MODBUS Slave, you can adjust the Delay Time to response to the MODBUS Master. Enter a Response Delay Time between 0ms (No delay) and 5000ms.
13 Wiring Details: Port 3 follows the RS-485 Communication Standard. Port 3 pin assignments are shown on the dialog. |
|
|
|
|
|
Related Topics: |
||
|
|
Help File Feedback and Comments |
|
THIS FEEDBACK IS ONLY FOR THE CLICK SOFTWARE HELP FILE!!! Click on the green text to submit Software Comments or feedback.
As a continued effort to provide the best products to our Customers, we provide this Feedback Page where you, the User, can easily communicate to us any issues, suggestions, and comments (good or bad) about this Help File. Your input is very important to us! Please take a minute to complete the information below. When finished, click the Send Feedback button and your email client will open with all the information already filled. If satisfied with the information, go ahead and send the email. Internet access and email account is required to send this email. Thank you for helping us provide top quality products and for trusting AutomationDirect with your automation needs and services.
If we use the information you provide or post your comments on the official Click PLC Web Site or any other publication, we will send you a small gift as a way of thanking you for your input. The gift depends on what's available at the moment and may consist of a Cap, T-shirt, a Cap, or some other ADC souvenir.
Complete the form provided below and click on the Send Feedback button when finished to open your email client and send the form. |